How Often Should Transformer Oil Be Tested?
Leave a message
The transformer oil testing cycle you're concerned about is indeed related to the long-term stable operation of the equipment. The testing cycle varies significantly depending on the type of equipment, voltage level, and operating conditions, and cannot be applied uniformly. The following is a detailed explanation based on comprehensive power industry standards and practical operation and maintenance experience:
Routine Inspection Cycle: Classified by voltage level and equipment type
220kV and above ultra-high voltage transformers
Dissolved gas analysis (DGA): Every 6 months
Routine oil quality testing (breakdown voltage, acid value, moisture, etc.): At least twice a year
Particle size testing: Every 3 years during operation, or additional testing when oil dielectric loss is abnormal
110kV and below transformers
DGA testing: Once a year
Routine testing: At least once a year
35kV and above distribution transformers (8MVA and above)
Oil sample testing cycle: Once a year
6~10kV distribution transformers
Belonging to secondary equipment, the routine oil sample testing cycle is generally once every 3 years. Withstand voltage testing can be performed annually.
100kVA and above service transformers, station service transformers