Primary Current Injector
video
Primary Current Injector

Primary Current Injector

1. Up to 1000 A AC Output: Ideal for primary injection testing of circuit breakers, CTs, switchgear, and protection systems.
2. Adjustable 0–400 V AC: Flexible voltage output to accommodate various test objects and requirements.
3. Integrated Measurement: Real-time parameter display and precise measurement of operating time and current.

Description

 

Primary Current Injection

What Is Primary Current Injection Testing?

 
Primary current injection feeds real high current through the primary conductor of the equipment under test. The current passes through the CT, secondary wiring and protection relay exactly as it would during an actual fault, and trips the breaker.
 
Because the whole chain carries the current, one test verifies three things at once: the CT ratio and phase angle are correct, the field wiring matches the design, and the relay picks up and trips at its set value and time. A secondary injection test can only verify the last of those.
 
Primary injectors are heavier, need more supply capacity, and each test takes longer to run. Most teams use primary injection for commissioning and periodic verification, and secondary injection for routine relay calibration.

 

 

Key Features of the HYPCIT Primary Current Injector
 

Up to 1000 A AC Current Output

Electric regulator-controlled current output up to 1000 A, suitable for primary injection testing of circuit breakers, CTs, switchgear and protection systems.

Adjustable AC Voltage Output (0–400 V)

Settable test voltage with automatic ramp function. Regulator output can also be used independently as a variable AC power supply.

7-Inch Touchscreen with Real-Time Display

800 × 480 color touchscreen shows output voltage, primary current and key electrical parameters in real time, eliminating the need for separate measurement equipment.

Built-In Resistance and Power Calculation

Samples primary voltage and current to calculate test resistance, active power, reactive power and power factor for circuit analysis.

Circuit Breaker Operating Time Measurement

Measures operating time under overcurrent or overvoltage conditions with 0.1 ms accuracy. Supports multiple tests and generates operating-time curves with settable current steps.

Data Output & Bilingual Interface

Built-in thermal printer for on-site records and RS232 interface for data upload. Chinese and English interface supported.

 

Technical Specifications

 

ParameterSpecification
Product SeriesHYPCIT
Maximum Current Output1000 A AC
AC Voltage Output0–400 V
Time Measurement Accuracy0.1 ms
Working VoltageAC 220 V ±10% / AC 380 V ±10%
Frequency50 Hz ±10%
Power Consumption≤60 W
Ambient Temperature0–40°C
Ambient Humidity≤90% RH
Display7-inch color LCD, 800 × 480
Communication InterfaceRS232
PrinterBuilt-in thermal printer
LanguageChinese / English
Dimensions460 × 340 × 200 mm
Weight10 kg

Note: Actual test configuration, connection method and required output should be confirmed according to the equipment under test and the applicable testing procedure.

 

Primary vs Secondary Injection

 

 Primary injectionSecondary injection
What it provesCT + wiring + relay + trip circuitRelay logic and settings only
Current levelUp to 1000A through the primary conductorMilliamps to a few amps at the relay terminals
Typical useCommissioning, acceptance, periodic verificationRoutine calibration, setting checks
EquipmentHeavier, needs higher supply capacityPortable, bench or field

→ See also: Secondary Current Injection Tester

Primary Current Injection Testing Applications
Primary Current Injection Testing Applications
  • Protection System Verification
    High current is injected into the main circuit of an operating line to simulate a fault. The test confirms the protection scheme trips as designed, at the correct current and within the correct time.
  • CT Ratio and Phase Angle Testing
    Current is injected into the CT primary side and the induced secondary current is measured with a compatible CT testing instrument, giving ratio difference and phase displacement directly.
  • Switchgear Stability and Temperature-Rise Testing
    Rated current is injected into the main circuit of a high-voltage switch and held, so stability can be assessed through the temperature-rise process.
  • General AC High-Current Source
    Also used as an AC high-current supply for power equipment and cable testing.

 

Why Choose Us

 

 
 

Typical Equipment Tested

Circuit breakers, current transformers (CTs), switchgear, protection systems, high-current electrical circuits, electrical cables and conductors.

 
 
 

Quality & Testing

Each unit is checked before shipment to verify electrical output, measurement functions and overall operating condition. Available documentation: CE marking, ISO 9001 certification, third-party calibration certificate (CNAS) and factory test report.

 
 
 

Technical Support & After-Sales Service

Our technical team assists with product selection, test application consultation, equipment operation and troubleshooting. Standard warranty: one year, with long-term maintenance support available after the warranty period.

 

 

FAQ

 

Q: What is a primary current injector used for?

A: A primary current injector is used to generate controlled high AC current and inject it directly into the primary circuit of electrical equipment. Typical applications include circuit breaker testing, current transformer testing, switchgear testing and protection system verification.

Q: What is the difference between primary and secondary injection testing?

A: Primary injection testing applies current directly to the primary circuit of the equipment under test, allowing the complete current path and associated protection components to be evaluated. Secondary injection testing applies a test signal to the secondary side of a protection or measurement circuit. The appropriate method depends on the equipment, test objective and applicable test procedure.

Q: What is the maximum current output of the HYPCIT Series?

A: The current page specifies a maximum electric regulator-controlled output of 1000 A.

Q: What equipment can the HYPCIT Series test?

A: The HYPCIT Series is suitable for circuit breaker testing, current transformer (CT) testing, switchgear testing, protection system verification and general AC high-current supply applications. For circuit breakers, it can measure operating time and generate operating-time curves. For CTs, it can evaluate ratio difference and phase displacement when used with a compatible CT testing instrument.

Q: Can the output current and voltage be adjusted?

A: The HYPCIT Series provides adjustable AC voltage output from 0 to 400 V and electric regulator-controlled current output up to 1000 A. The required operating range should be selected according to the test object and application.

Q: What information should I provide when requesting a quotation?

A: To recommend a suitable configuration, please provide: test object, required maximum current, required test voltage, power supply available at the test site, intended testing application, required test duration, and applicable testing standard (if available). Our engineers can review these requirements before quotation.

Q: What documents are available with the equipment?

A: Depending on the product and order requirements, documentation may include CE marking, ISO 9001 certification, third-party calibration documentation and a factory test report.

Q: What is the warranty period?

A: The standard warranty period is one year. Long-term maintenance and technical support can also be provided after the warranty period.

 

 

 

 

Hot Tags: primary current injector, China primary current injector manufacturers, suppliers, factory, primary current injection, current injection tester, current injection test set, secondary current injection test, secondary injection test set, Primary Current Injector