High Current Injecting Set

High Current Injecting Set

1. High Current Output: Adjustable output from 500A to 25,000A for high-power primary injection testing.
2. Flexible Configuration: Available in integrated or separated (control unit + booster) setups based on total capacity.
3. Wide Test Scope: Ideal for circuit breakers, current transformers, switchgear, protection systems, and cables.
4. High Performance: Low distortion (<5%) with stable current adjustment and digital/analog display options.
5. Versatile Applications: Supports lab, field commissioning, and power supply of AC 220V / 400V.

Description

 

 

High Current Injection Test Set (SLQ Series, 500A – 25000A)

 

The SLQ is our basic high current injection set: a stepless AC current source covering 500A to 25000A. It injects current into the primary circuit of the equipment under test to reproduce rated load current or fault current - and that is all it does.
 
If your test procedure also requires proving breaker operating times and plotting time-current curves, you need the HYPCIT, our advanced model.
 
High Current Injecting Set

What Is a High Current Injecting Set?

 

A high current injecting set is a primary injection test system that generates and delivers a controlled high AC current directly into the primary circuit of electrical equipment.
 
Unlike secondary injection testing, which applies a simulated signal to a relay, primary injection tests the actual primary current path. This allows you to verify the combined performance of the entire loop, including current transformers, circuit breakers, conductors, and connections under real load conditions.
 
The SLQ-2000A series is designed for applications requiring large test currents to simulate rated or fault conditions. Depending on the capacity, it is available in an integrated enclosure or a split configuration (control unit + booster) to ensure stable output up to 25,000 A.

 

Key Features

Stepless output adjustment

output current is polar-free and rises smoothly across the full range

Wide load variation range

stable output across a broad range of load impedances

Internal CT measurement with meter options

output current is measured via an internal CT in the booster, with analog or 4½-digit digital current meter (Class 0.5) available to customer requirement

General-purpose AC high-current source

usable for power equipment and cable testing beyond switchgear and CT work

 

Technical Specifications

 

ParameterSpecification
ModelSLQ-2000A
Power SupplyAC 220V / AC 400V
Frequency45–65 Hz
Maximum Output Current500A–25,000A
Impedance Voltage8%
Idle Current6%
Current Distortion<5%
Current MeasurementInternal current transformer
Current DisplayAnalog or 4½-digit digital meter
Display AccuracyClass 0.5
Working Temperature0–40°C
Working Humidity<90% RH
ConfigurationIntegrated or separate type

Note: Actual power supply voltage and output configuration depend on the required output capacity.

 

SLQ or HYPCIT: Which Primary Injection Set Do You Need?

 SLQ - basicHYPCIT - advanced
FunctionCurrent injection onlyCurrent injection + breaker operating time measurement + time-current curve plotting
Output current500A – 25000A1000A / 2000A standard, higher ratings to order
Output adjustmentStepless, smooth riseSettable voltage, current and automatic ramp
MeasurementOutput current via internal CT; analog or 4½-digit meter, Class 0.5Impedance voltage, power factor, resistance, active and reactive power, operating time to 0.1 ms
InterfaceAnalog or digital meter display7-inch touch LCD, built-in thermal printer, RS232
ConfigurationIntegral ≤5 kVA; split control unit + booster above 5 kVA 
Choose it whenYou need high current and timing is measured separatelyThe set must also prove trip times

Related Products:
→ Primary Current Injector (HYPCIT, up to 1000 A)
→ Secondary Current Injection Tester

 

Circuit breaker verification by using High Current Injecting Set
Main Testing Applications
  • Circuit breaker verification - Injects rated or fault current into the breaker main circuit to assess stability and temperature-rise under real primary current.
  • Protection scheme proving - Injects simulated fault current to confirm protection systems trip at the correct current and within the specified time.
  • CT testing, with an external error meter - The SLQ injects high current into the CT primary side. Ratio error and phase displacement are then read from the secondary with a separate CT error meter, which is not part of the set.
  • Temperature-rise testing - Serves as an AC high-current source for busbars, cables, switchgear, and industrial equipment.

 

FAQ

 

Q: What output current do I need?

A: Match the set to the highest CT primary rating or breaker rating you plan to test. Medium-voltage distribution equipment is generally covered below 1000 A - see the HYPCIT Primary Current Injector. For HV and EHV switchgear, large CTs, busbars and cables, the SLQ covers 500 A to 25,000 A.

Q: What is the difference between the integral and split configuration?

A: Up to 5 kVA total output capacity, the control unit and current booster are in one enclosure. Above 5 kVA they are supplied as two separate enclosures. The configuration is decided by the capacity you specify, not chosen separately.

Q: How is output current measured?

A: From the secondary of a current transformer built into the booster, so the reading is a direct measurement of actual output. You can specify an analog meter or a 4½-digit digital meter, both accuracy class 0.5.

Q: Is the output current adjustable in steps?

A: No. Adjustment is stepless across the full range, with smooth current rise and stable output over a wide load variation range.

Q: What supply does it require?

A: AC 220V or AC 400V, 45–65 Hz. The required supply voltage depends on the output capacity of the set - see the model selection table.

Q: Can the SLQ test CT ratio and phase angle?

A: Not on its own. The SLQ supplies the primary current; ratio error and phase displacement are read from the CT secondary with a separate error meter, which is not part of the SLQ set. If you need that measurement built in, ask about the HYPCIT.

 

 

 

 

Hot Tags: high current injecting set, China high current injecting set manufacturers, suppliers, factory, primary current injection, current injection tester, current injection test set, secondary current injection test, secondary injection test set, Primary Current Injector