High Current Injecting Set
1. High Current Output: Adjustable output from 500A to 25,000A for high-power primary injection testing.
2. Flexible Configuration: Available in integrated or separated (control unit + booster) setups based on total capacity.
3. Wide Test Scope: Ideal for circuit breakers, current transformers, switchgear, protection systems, and cables.
4. High Performance: Low distortion (<5%) with stable current adjustment and digital/analog display options.
5. Versatile Applications: Supports lab, field commissioning, and power supply of AC 220V / 400V.
Description
High Current Injection Test Set (SLQ Series, 500A – 25000A)

What Is a High Current Injecting Set?
Key Features
Stepless output adjustment
output current is polar-free and rises smoothly across the full range
Wide load variation range
stable output across a broad range of load impedances
Internal CT measurement with meter options
output current is measured via an internal CT in the booster, with analog or 4½-digit digital current meter (Class 0.5) available to customer requirement
General-purpose AC high-current source
usable for power equipment and cable testing beyond switchgear and CT work
Technical Specifications
| Parameter | Specification |
| Model | SLQ-2000A |
| Power Supply | AC 220V / AC 400V |
| Frequency | 45–65 Hz |
| Maximum Output Current | 500A–25,000A |
| Impedance Voltage | 8% |
| Idle Current | 6% |
| Current Distortion | <5% |
| Current Measurement | Internal current transformer |
| Current Display | Analog or 4½-digit digital meter |
| Display Accuracy | Class 0.5 |
| Working Temperature | 0–40°C |
| Working Humidity | <90% RH |
| Configuration | Integrated or separate type |
Note: Actual power supply voltage and output configuration depend on the required output capacity.
SLQ or HYPCIT: Which Primary Injection Set Do You Need?
| SLQ - basic | HYPCIT - advanced | |
| Function | Current injection only | Current injection + breaker operating time measurement + time-current curve plotting |
| Output current | 500A – 25000A | 1000A / 2000A standard, higher ratings to order |
| Output adjustment | Stepless, smooth rise | Settable voltage, current and automatic ramp |
| Measurement | Output current via internal CT; analog or 4½-digit meter, Class 0.5 | Impedance voltage, power factor, resistance, active and reactive power, operating time to 0.1 ms |
| Interface | Analog or digital meter display | 7-inch touch LCD, built-in thermal printer, RS232 |
| Configuration | Integral ≤5 kVA; split control unit + booster above 5 kVA | |
| Choose it when | You need high current and timing is measured separately | The set must also prove trip times |
Related Products:
→ Primary Current Injector (HYPCIT, up to 1000 A)
→ Secondary Current Injection Tester

Main Testing Applications
- Circuit breaker verification - Injects rated or fault current into the breaker main circuit to assess stability and temperature-rise under real primary current.
- Protection scheme proving - Injects simulated fault current to confirm protection systems trip at the correct current and within the specified time.
- CT testing, with an external error meter - The SLQ injects high current into the CT primary side. Ratio error and phase displacement are then read from the secondary with a separate CT error meter, which is not part of the set.
- Temperature-rise testing - Serves as an AC high-current source for busbars, cables, switchgear, and industrial equipment.
FAQ
Q: What output current do I need?
A: Match the set to the highest CT primary rating or breaker rating you plan to test. Medium-voltage distribution equipment is generally covered below 1000 A - see the HYPCIT Primary Current Injector. For HV and EHV switchgear, large CTs, busbars and cables, the SLQ covers 500 A to 25,000 A.
Q: What is the difference between the integral and split configuration?
A: Up to 5 kVA total output capacity, the control unit and current booster are in one enclosure. Above 5 kVA they are supplied as two separate enclosures. The configuration is decided by the capacity you specify, not chosen separately.
Q: How is output current measured?
A: From the secondary of a current transformer built into the booster, so the reading is a direct measurement of actual output. You can specify an analog meter or a 4½-digit digital meter, both accuracy class 0.5.
Q: Is the output current adjustable in steps?
A: No. Adjustment is stepless across the full range, with smooth current rise and stable output over a wide load variation range.
Q: What supply does it require?
A: AC 220V or AC 400V, 45–65 Hz. The required supply voltage depends on the output capacity of the set - see the model selection table.
Q: Can the SLQ test CT ratio and phase angle?
A: Not on its own. The SLQ supplies the primary current; ratio error and phase displacement are read from the CT secondary with a separate error meter, which is not part of the SLQ set. If you need that measurement built in, ask about the HYPCIT.