Description
Voltage transformer tester HYVA-404 is a PT Analyzer.
Features
Tests for Voltage Transformer:
1) Ratio error and phase error test of PT
2) Excitation curve test of PT
3) PT Secondary burden test
4) Winding resistance test of PT primary and secondary
5) PT and CVT ratio error test with 4KV voltage booster
6) PT induce voltage withstand test
General functions
1)Making word report automatic
2)Tester can be operated by laptop through Ethernet port
3)PC application support bulk report making
Technical Specification
1) Test standards: IEC60044-2, IEC60044-5, IEC60044-61869, C57.13
2) Power supply: AC220V±10%, 50/60Hz±10%
3) Voltage output: 0.1~160V AC(AC 0-4KV with external voltage booster)
4) Current output: 0.001~5A(RMS), Peak value 15A
5) Power output: 500VA
6) Maximum knee voltage measurement: 45KV
7) Current measurement:
Range: 0~10A (automatically change range in 0.004/0.04/0.4/2/10A auto range)
Error: <±0.1%+0.01%FS
8) Voltage measurement:
Range: 0~200V (automatically change range in 1V/10V/120V/240V auto range)
Error: < ±0.1%+0.01%FS
9) Winding resistance measurement:
Range: 0~10kΩ (automatically change range in 2ohm/20ohm/160ohm/1kohm/10kohm auto range)
Error: < 0.2%RDG+0.02%FS
Maximum resolution: 0.1mΩ
10) Temperature measurement:-50~100 Celsius degree; error<3 Celsius degree
11) PT Secondary burden and admittance test:
Burden Range: 0~80kohm (automatically change range in 320ohm/5.3kohm/80kohm auto range)
Admittance Range: 0-100mS
Error :<0.2%RDG+0.02%FS
Maximum resolution: 0.1ohm
12)PT ratio measurement:
Range: 1~30000
1~2000 error<0.1%
2000~10000 error<0.2%
10000~30000 error<0.5%
With 4KV voltage booster ratio measurement at comparison mode: 1-2200 error <0.05%
13) PT ratio error measurement phase error <30min, resolution 0.1min, with 4KV booster ratio measurement at comparison mode phase error <3min
14) PT excitation mode ratio error measurement. Ratio error <0.1%, phase Error<3min
15) CVT ratio measurement 1-2200 error< 0.05%(with 4kv voltage booster only)
16)Make evaluation for test results according to selected standards
17) Make word report for all test results
18) Memory capacity: >30000 groups test results
19)Working condition: temperature: -10℃~50℃; moist: ≤90%
20) Size: 485mm×356mm×183mm
21) Weight: <15kg
Hot Tags: voltage transformer tester, China voltage transformer tester manufacturers, suppliers, factory, Voltage Transformer Tester, ct pt tester, PT Analyzer, pt ct test, Multi Function CT Test Set, Advanced Current Transformer Tester With Touchscreen