CT PT Analyzer
CT PT Analyzer HYVA-405 is used to measure all kinds of current transformer and voltage transformer. It can calculate the ratio errors and phase angle errors of current transformer and voltage transformer at rated burden and working burden in one time test. The tester can automatically evaluate the test results according to the selected standard to determine whether the transformer is qualified.
Description
CT PT Analyzer HYVA-405 is used to measure all kinds of current transformer and voltage transformer. It can calculate the ratio errors and phase angle errors of current transformer and voltage transformer at rated burden and working burden in one time test. The tester can automatically evaluate the test results according to the selected standard to determine whether the transformer is qualified.
Features
1.Tests for Current Transformer:
1)Ratio error and phase error test for all CTs
2)Excitation curve and knee point test for all CTs
3)Instrument factor FS test of measurement CTs
4)Accuracy limit factor ALF measurement of protection CTs
5)CT Winding resistance measurement
6)Short current factor Kssc and dimension factor Ktd test for transient protection CTs
7)CT polarity test
8)CT secondary burden test
9)CT nameplate deduce
10) Test multi taps CT with switch box
11) Test bush CT inside body of power transformer
2.Tests for Voltage Transformer:
1) Ratio error and phase error test of VT
2) Excitation curve test of VT
3) VT Secondary burden test
4) Winding resistance test of VT primary and secondary
5) VT and CVT ratio error test with 4KV voltage booster
6) VT induce voltage withstand test
3. General functions:
1) Making word report automatic
2) Auto comparison of test results and standard requirements. And then give conclusion pass or fail for sample CT
3) Tester can be operated by laptop through Ethernet port
4) PC application support bulk report making
Technical Specification
1) Test standards: IEC60044-1, IEC60044-6, IEC60044-2, IEC60044-5, IEC60044-61869, GB-1207, GB-1208, GB-16849, C57.13
2) Power supply: AC220V±10%, 50/60Hz±10%
3) Voltage output: 0.1~160V AC(AC 0-4KV with external voltage booster)
4) Current output: 0.001~5A(RMS), Peak value 15A
5) Power output: 500VA
6) Maximum knee voltage measurement: 45KV
7) Current measurement:
Range: 0~10A (automatically change range in 0.004/0.04/0.4/2/10A auto range)
Error: <±0.1%+0.01%FS
8) Voltage measurement:
Range: 0~200V (automatically change range in 1V/10V/120V/240V auto range)
Error: < ±0.1%+0.01%FS
9) Turns ratio measurement:
Range:1~35000
1~2000 error<0.05%
2000~5000 error<0.1%
5000~35000 error<0.2%
10) Ratio error of CT: Typical <0.02%, Assured <0.1%, Resolution <0.01%
11) Phase measurement: error < 2min; resolution: 0.01min
11) Winding resistance measurement:
Range: 0~10kΩ (automatically change range in 2ohm/20ohm/160ohm/1kohm/10kohm auto range)
Error: < 0.2%RDG+0.02%FS
Maximum resolution: 0.1mΩ
12)Temperature measurement:-50~100 Celsius degree; error<3 Celsius degree
13)CT Secondary burden:
Range: 0~160ohm (automatically change range in 2ohm/20ohm/160ohm auto range)
Error: <0.2%RDG+0.02%FS
Maximum resolution: 0.001ohm
14)PT Secondary burden and admittance test:
Burden Range: 0~80kohm (automatically change range in 320ohm/5.3kohm/80kohm auto range)
Admittance Range: 0-100mS
Error :<0.2%RDG+0.02%FS
Maximum resolution: 0.1ohm
15)PT ratio measurement:
Range: 1~30000
1~2000 error<0.1%
2000~10000 error<0.2%
10000~30000 error<0.5%
With 4KV voltage booster: 1-2200 error <0.05%
16) VT ratio error measurement phase error <30min, resolution 0.1min
17) VT excitation mode ratio error measurement. Ratio error <0.1%, phase Error<3min
17) CVT ratio measurement 1-2200 error< 0.05%(with 4kv voltage booster only)
18)Make evaluation for test results according to selected standards
19) Make word report for all test results
20) Bulk report application could make more than 1000 test records in once a time
21) Measure the ratio errors and phase angle errors at rated burden and working burden in one time.
22) Compare excitation curves with saved excitation curves in the same window
23) Memory capacity: >30000 groups test results
24)Working condition: temperature: -10℃~50℃; moist: ≤90%
25) Size: 485mm×356mm×183mm
26) Weight: <15kg
Hot Tags: ct pt analyzer, China ct pt analyzer manufacturers, suppliers, factory, Voltage Transformer Tester, ct pt tester, PT Analyzer, pt ct test, Multi Function CT Test Set, Advanced Current Transformer Tester With Touchscreen